The main types of current transformer (CT) are wound-primary, toroidal (window), bar-type, split-core, bushing and summation CTs. All of them produce a small, safe secondary current, usually 5 A or 1 A, that is proportional to a much larger current in the primary conductor, so meters and protective relays can measure it. They differ in how the primary passes through the core, how they are installed and whether they are built for accurate metering or for protection during faults.
This guide explains how current transformers work, describes each type with its strengths and limits, compares metering and protection classes, shows how to read a CT nameplate, and gives a practical step-by-step method for choosing the right one, along with the safety rules every installer needs to know.
Transformers in Brief
A transformer is a static device that transfers electrical energy between AC circuits through electromagnetic induction. In practice, a transformer converts alternating current (AC) from one voltage level to another, stepping it up or down without changing the frequency. It has a primary and a secondary winding on a shared magnetic core; the ratio of turns between them sets the ratio of voltages and, inversely, of currents.
Power transformers are designed to move energy efficiently. Instrument transformers, which include current transformers and voltage (potential) transformers, are designed to measure. Their job is to reproduce the primary quantity accurately at a scaled-down level that instruments can handle safely, while isolating those instruments from the high-voltage system.
What Is a Current Transformer and How Does It Work?
A current transformer has very few primary turns, often just one, which is the conductor itself passing through the core, and many secondary turns. Because ampere-turns balance on both sides, the secondary current equals the primary current divided by the turns ratio. A 400:5 CT, for example, delivers 5 A on its secondary when 400 A flows in the primary, and 2.5 A when 200 A flows.
That scaled current feeds ammeters, energy meters, power quality analyzers and protective relays. CTs also provide electrical isolation, keeping instruments and the people reading them away from high-voltage conductors. Unlike a power transformer, a CT’s secondary current is set by the primary current flowing through the circuit, not by the load connected to it, which is why it behaves like a current source.
Worked example
Suppose a 600:5 CT is installed on a feeder and the connected meter reads 3.2 A on the secondary. The primary current is 3.2 × (600 ÷ 5) = 3.2 × 120 = 384 A. Meters are usually programmed with the CT ratio so they display primary amps directly, which is why labeling the ratio at the panel matters: a wrong ratio setting produces readings that look plausible but are badly off.
Key safety rule: never open the secondary circuit of a CT while the primary is energized. With no secondary load, the CT tries to drive its current into an open circuit, which can generate dangerously high voltages, damage insulation and injure anyone nearby. Secondaries should always be connected to a burden or shorted through a shorting terminal block before instruments are removed.
Types of Current Transformer
1. Wound-primary current transformer
A wound CT has a primary winding of one or more turns built into the transformer, with terminals you connect in series with the circuit. Because it can have several primary turns, it can produce accurate readings at relatively low primary currents, where a single-turn design would struggle to deliver enough ampere-turns. Wound CTs are common in metering for smaller loads and in medium-voltage switchgear.
2. Toroidal (window) current transformer
A toroidal CT has a ring-shaped core with the secondary wound around it and no built-in primary. The cable or busbar passes through the center “window” and acts as a single-turn primary. They are compact, inexpensive and very common in low-voltage panels, motor control centers and building energy monitoring. Solid toroidal CTs must be installed before the conductor is terminated, because the ring cannot open. A useful trick for low currents is to loop the conductor through the window more than once: two passes through a 100:5 CT effectively make it a 50:5 CT.
3. Bar-type current transformer
A bar-type CT includes a solid copper or aluminum bar that passes through the core and serves as the single-turn primary. It is bolted directly into a busbar system, which makes it robust under high currents and short-circuit forces. Bar-type CTs are widely used in switchboards and for protective relaying.
4. Split-core current transformer
A split-core CT is a window CT whose core opens on a hinge or separates into two halves, so it can be clamped around an existing conductor without disconnecting it. This makes it the go-to choice for retrofits, temporary monitoring and energy audits. The trade-off is slightly lower accuracy than a solid core, because the joint in the core adds a small air gap. Keeping the mating faces clean and fully latched is the simplest way to protect accuracy.

5. Bushing current transformer
Bushing CTs are toroidal CTs mounted around the bushings of high-voltage equipment such as power transformers and circuit breakers. The bushing conductor is the primary. Because they sit inside existing equipment, they save space and cost in substations and are mainly used for protection. Many are multi-ratio, with taps on the secondary so the ratio can be chosen at commissioning.
6. Summation current transformer
A summation CT combines the secondary outputs of several main CTs into one output, so a single meter can register the total current of multiple feeders. The main CTs feeding it must have the same ratio and be on the same phase and voltage system. Summation CTs are used where a site has several incoming supplies but needs one combined measurement.
A related device: the Rogowski coil
Rogowski coils are flexible, air-cored sensors that wrap around a conductor. Strictly speaking they are not CTs, since they output a voltage proportional to the rate of change of current and need an integrator. They are lightweight, do not saturate and suit large or awkward conductors, so they are often used for portable measurements and power quality studies.
Current Transformer Types Compared
| Type | Primary | Typical use | Install without disconnecting? |
|---|---|---|---|
| Wound | Built-in winding, one or more turns | Accurate metering at lower currents | No |
| Toroidal (window) | Cable or bus through the ring | Panels, motor circuits, energy monitoring | No |
| Bar-type | Built-in solid bar | Switchboards, protection | No |
| Split-core | Cable through an opening core | Retrofits, audits, temporary monitoring | Yes |
| Bushing | Equipment bushing conductor | Substation protection | Built into equipment |
| Summation | Secondaries of other CTs | Totalizing several feeders | Wired into CT circuits |
Metering CTs vs Protection CTs
Beyond physical construction, CTs are split by purpose. Metering CTs must be very accurate across normal load currents but are designed to saturate during faults, which protects connected meters. Protection CTs must stay reasonably accurate at many times their rated current, so relays can detect and clear faults correctly.
- In North America (IEEE C57.13): metering classes include 0.3, 0.6 and 1.2 (percent error at rated conditions); relaying classes are written like C100, C200, C400 or C800, where the number indicates the secondary terminal voltage the CT can deliver at 20 times rated current without exceeding a set error.
- Internationally (IEC 61869-2): metering classes include 0.1, 0.2, 0.5 and 1, with 0.2S and 0.5S for extended low-current accuracy; protection classes are written like 5P20, meaning 5% composite error at 20 times rated current.
Using a metering CT for relay protection is a common and serious mistake. During a fault it may saturate exactly when the relay needs an accurate signal, which can delay or prevent tripping. The reverse mistake, using a protection CT for revenue metering, usually produces readings that are not accurate enough at normal loads.
How to Read a Current Transformer’s Rating
- Ratio: for example 600:5, meaning 600 A primary gives 5 A secondary.
- Secondary current: 5 A is standard in North America; 1 A is common elsewhere and for long cable runs, because it reduces losses in the leads.
- Burden: the load the CT can drive while staying in its accuracy class, given in VA or ohms. It includes the meter or relay plus the resistance of the secondary wiring.
- Accuracy class: as described above.
- Insulation level and system voltage: the CT must be rated for the voltage of the conductor it surrounds.
- Thermal and short-time ratings: how much continuous overload and fault current it can survive.
- Polarity marks: H1 and X1 (or P1 and S1) show the direction of current flow, which matters for power and directional measurements.
Why burden matters
Burden is where many installations go wrong. A long run of thin secondary wire adds resistance, and that resistance counts toward the CT’s burden just like the meter does. If the total exceeds the CT’s rating, accuracy drops and protection CTs may saturate early. Shorter leads, a larger wire gauge or a 1 A secondary are the usual fixes.
How to Choose the Right Current Transformer
- Define the job. Billing-grade metering, general monitoring or protection each point to different accuracy classes.
- Size the ratio. Pick a primary rating a little above normal maximum load, so the CT operates in its accurate range most of the time.
- Check the physical fit. Window size must fit the cable or busbar, and you need to decide between solid and split-core.
- Calculate the burden. Add instrument burden and lead resistance and confirm the CT is rated for it.
- Match the instrument. Make sure the meter or relay accepts the CT’s secondary rating (5 A, 1 A or a low-voltage output).
- Confirm standards and approvals. Utility metering and code-governed installations often require specific certified products.
Common selection mistakes
- Oversizing the ratio “for safety”, so the CT spends most of its life at a small fraction of rated current where accuracy is poorest.
- Ignoring lead resistance when calculating burden.
- Mixing up polarity, which makes power readings negative or nonsensical.
- Choosing a split-core CT for billing-grade metering where a solid core is required.
Installation and Safety Basics
CT installation should be done by qualified electricians following the manufacturer’s instructions, the National Electrical Code and workplace electrical safety practices such as NFPA 70E. Good practice includes de-energizing where possible, observing polarity marks, grounding the secondary circuit at one point, using shorting terminal blocks and labeling CT ratios on panels so future technicians can interpret readings correctly.
Where Current Transformers Are Used
- Utility revenue metering at substations and large customer sites.
- Overcurrent, differential and ground fault protection schemes.
- Building energy management and submetering of tenants or equipment.
- Motor protection and monitoring in industrial plants.
- Solar, battery and backup generator systems, where monitoring load helps size and control equipment, as in a whole house generator installation.
- HVAC diagnostics, where clamp-on current measurements help technicians check compressors and fans, including in systems like high velocity air conditioning.
Frequently Asked Questions
What are the main types of current transformer?
The main types are wound-primary, toroidal (window), bar-type, split-core, bushing and summation CTs. They differ mainly in how the primary conductor passes through the core and how they are installed.
What is the difference between a current transformer and a potential transformer?
A current transformer scales down current and is connected in series with the circuit. A potential (voltage) transformer scales down voltage and is connected in parallel across the circuit.
Why should a CT secondary never be left open?
With the primary energized and no secondary load, the CT can produce very high voltages that damage insulation and create a serious shock hazard. Always short the secondary before disconnecting instruments.
What does a CT ratio of 400:5 mean?
It means 400 A flowing in the primary produces 5 A in the secondary. Readings scale proportionally, so 200 A in the primary gives 2.5 A.
When should I use a split-core CT?
Use a split-core CT when you need to add monitoring to an existing circuit without disconnecting conductors, such as for retrofits, energy audits or temporary measurements.
Should I choose a 5 A or 1 A secondary?
A 5 A secondary is the North American standard and suits short lead runs. A 1 A secondary reduces wiring losses and burden on long runs, so it is often preferred when the meter or relay is far from the CT.
Bottom Line on Current Transformers
Pick the CT type by how it must be installed (solid, split-core, bar or bushing), then pick the class by purpose: metering accuracy for billing and monitoring, relaying class for protection. Size the ratio close to real maximum load, check the total burden including the wiring, and never open a live secondary. For more practical guides from around the site, you might also like How to Choose the Right Tie for Your Suit.
This article is general information only. Electrical work can be dangerous and should be carried out by a qualified professional in line with local codes.



